Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv

Product Details
Customization: Available
Range of Application: Power Measurement
Frequency Characteristics: Power Frequency
Manufacturer/Factory, Trading Company
Diamond Member Since 2024

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Importers and Exporters
The supplier has import and export rights
High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
to see all verified strength labels (11)
  • Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
  • Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
  • Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
  • Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
  • Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
  • Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
Find Similar Products
  • Overview
  • Product Description
  • Detailed Photos
  • Product Parameters
  • Fields of application
  • After Sales Service
  • Packaging & Shipping
  • FAQ
Overview

Basic Info.

Model NO.
BKGKL-
Core
Air Core
Usage
Single-Phase Transformer, Power Transformer, Distr
Shape of Core
Ring
Voltage Level
10/35kv
Rated Frequency
50Hz
Transport Package
Wooden Case
Specification
Voltage 10KV-500KV, Current100A-20000A
Trademark
HZEC
Origin
China
HS Code
8504500000
Production Capacity
30000 Sets/Year

Product Description

Product Description

Henan Energy Electric Equipment Co., Ltd. was established in 2011 and is an excellent and reliable power equipment manufacturer in China. The company mainly develops and produces oil-immersed transformers, dry-type transformers, box-type substations, high-voltage switches, and medium and low voltage complete sets of equipment. The equipment put into production and operation of the project advocates energy saving, intelligence, informatization, and mechanization. The company has established the Henan Triangle Energy-saving Transformer Engineering Technology Research Center, with 71 utility model patents and 15 invention patents. With years of accumulation in the transformer industry and strong technological innovation capabilities, HZEC products are sold to the Middle East, North America, South America, Europe, Southeast Asia, Africa, and other regions, covering more than 40 countries.Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv

Dry-type air-core current-limiting reactor
The concept and principle of reactors 
 The reactor is a passive electronic component that is equally important as a capacitor and an inductor. Its function is similar to that of a capacitor, but it stores electromagnetic energy rather than electrical energy. It can adjust the voltage and current of the AC circuit to achieve the purpose of energy saving, voltage stabilization and noise reduction. 
 The principle of the reactor is based on the inductive properties of the steel core and coil, which realizes the adjustment of the circuit by hindering the speed and direction of the electronic flow. When the alternating current passes through the reactor, due to the change of the current in the circuit, an induction voltage perpendicular to the direction of the flow will be generated, thus adjusting the current in the circuit. 


Product Application
XKGKL,,,.
XKGKL series current-limiting reactors are connected in series with the system circuit to strengthen the system impedance.Reduce the short-circuit current in case of malfunction with the system, which will lower the fault current to the allowable value.

Model Definition
 
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv

Ordering Information
           Nominal system voltage
           Rated continuous current
           Rated reactance rate
          Rated reactance
          Rated short-time current
          Mode of installation (horizontal or vertical)
          Working environment (indoors or outdoors)
          Angle between inlet and outlet
         Other special requirement
Product Standard

GB/T 1094.6-2011     IEC 60076-6:2007
GB/T 1094.1-2011     IEC 60076-1:2011
GB/T 1094.3-2017     IEC 60076-3:2013
Detailed Photos
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv

 

Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
 
Product Parameters

Dry-type air-core current-limiting reactor 10kV
 

 Part No.

Rated current
A


Rated
reactance rate


Rated reactance
Ω


Short-
 time
current
kA


Single- phase
power
kvar


Single- phase loss75C
kW

Overall dimension


Pitch diameter
Dc
mm


Weight
(per
phase)
 kg



Suggested arrangement mode
Ds
mm
H
mm
XKGKL-10-800-5 800 5% 0.361 16.00 230.9 4.6 1270 770 1170 350
side by side
XKGKL-10-800-8 8% 0.577 10.00 369.5 5.7 1380 840 1280 420
XKGKL-10-800-10 10% 0.722 8.00 461.9 6.5 1480 890 1380 490
XKGKL-10-800-12 12% 0.866 6.67 554.3 7.7 1530 940 1430 547
XKGKL-10-1000-5 1000 5% 0.289 20.00 288.7 6.0 1330 710 1240 370
XKGKL-10-1000-8 8% 0.462 12.50 461.9 7.2 1480 820 1380 530
XKGKL-10-1000-10 10% 0.577 10.00 577.4 8.7 1670 760 1480 580
XKGKL-10-1000-12 12% 0.693 8.33 692.8 9.8 1670 820 1480 630
XKGKL-10-1500-5 1500 5% 0.192 30.00 433.0 8.1 1380 730 1200 477
XKGKL-10-1500 8 8% 0.308 18.75 692.8 9.4 1590 780 1320 662
XKGKL-10-1500-10 10% 0.385 15.00 866.1 11.3 1590 850 1330 718
XKGKL-10-1500-12 12% 0.462 12.50 1039.3 12.8 1700 880 1430 857
XKGKIA0-2000/5 2000 5% 0.144 40.00 577.4 9.1 1710 600 1580 544
XKGKL-10-2000-8 8% 0.231 25.00 923.8 11.6 1770 700 1590 746
XKGKL-10-2000-10 10% 0.289 20.00 1154.7 13.5 1870 730 1680 778
XKGKL-10-2000-12 12% 0.346 16.67 1385.7 14.9 1860 800 1680 1000
XKGKL-10-2500-5 2500 5% 0.115 50.00 721.7 10.2 1544 790 1280 678
XKGKL-10-2500-8 8% 0.185 31.25 1154.7 13.7 1600 960 1330 946
XKGKL-10-2500-10 10% 0.231 25.00 1443.4 15.3 1740 980 1480 1085
XKGKL-10-2500-12 12% 0.277 20.83 1732.1 18.1 1730 1000 1460 1200
XKGKL-10-3000-5 3000 5% 0.096 60.00 866.0 11.2 1620 830 1440 733
XKGKL-10-3000-8 8% 0.154 37.50 1386.0 15.1 1720 930 1540 975
XKGKL-10-3000-10 10% 0.192 30.00 1732.0 17.5 1750 1130 1650 1103
XKGKL-10-3000-12 12% 0.231 25.00 2079.0 19.1 1760 1030 1500 1253
XKGKL-10-3500-5 3500 5% 0.082 70.00 1010.0 12.7 1700 800 1440 980
XKGKL-10-3500-8 8% 0.132 43.75 1617.0 15.7 1820 880 1710 1322
XKGKL-10-3500-10 10% 0.165 35.00 2021.0 18.9 1820 950 1710 1500
XKGKL-10-3500-12 12% 0.198 29.17 2425.0 20.1 1820 1020 1710 1700
XKGKL-10-4000-5 4000 5% 0.072 80.00 1155.0 12.1 1750 800 1640 1058
XKGKL-10-4000 8 8% 0.115 50.00 1848.0 17.8 1880 880 1700 1461
XKGKL-10-4000-10 10% 0.144 40.00 2309.0 20.7 1970 880 1700 1687
XKGKL-10-4000-12 12% 0.173 33.33 2771.0 22.6 2010 930 1740 1833


35kV series
  
Part No.


Rated current
A


Rated
reactance rate


Rated reactance
Ω


Short-
 time
current
kA


Single- phase
power
kvar


Single- phase loss75C
kW

Overall dimension


Pitch diameter
Dc
mm


Weight
(per
phase)
 kg



Suggested arrangement mode
Ds
mm
H
mm
XKGKL-35-200-4 200 4% 4.042 5.00 161 3.8 1590 600 1130 340
side by side
XKGKL-35-200-5 5% 5.052 4.00 202 4.7 1640 630 1180 410
XKGKL-35-200-6 6% 6.062 3.33 242 5.2 1700 630 1180 480
XKGKL-35-200-8 8% 8.083 2.50 323 6.3 1760 650 1570 560
XKGKL-35-400-5 400 5% 2.256 8.00 404 6.7 1780 730 1330 670
XKGKL-35-400 8 8% 4.042 5.00 646 8.4 1700 690 1510 880
XKGKL-35-400-10 10% 5.052 4.00 808 9.6 2000 680 1810 970
XKGKL-35-400 12 12% 6.062 3.33 970 10.7 2000 730 1810 1050
XKGKL-35-600-5 600 5% 1.684 12.00 606 8.2 1680 650 1550 850
XKGKL-35-600-8 8% 2.694 7.50 970 10.5 1980 700 1790 1120
XKGKL-35-600-10 10% 3.368 6.00 1212 12.9 1980 780 1790 1340
XKGKL-35-600-12 12% 4.042 5.00 1454 13.8 2030 800 1840 1520
XKGKL-35-800-5 800 5% 1.263 16.00 808 9.4 1800 650 1600 980
XKGKL-35-800-8 8% 2.021 10.00 1293 13.3 2100 650 1920 1420
XKGKL-35-800-10 10% 2.526 8.00 1616 14.9 2100 830 1920 1650
XKGKL-35-800-12 12% 3.031 6.67 1939 16.5 2100 760 1920 1720
XKGKL-35-1000-5 1000 5% 1.010 20.00 1010 10.2 1670 700 1540 1270
XKGKL-35-1000 8 8% 1.617 12.50 1616 14.2 1870 800 1680 1620
XKGKL-35-1000-10 10% 2.021 10.00 2020 16.9 1940 800 1750 1740
XKGKL-35-1000 12 12% 2.425 8.33 2424 18.6 2070 880 1880 1870
XKGKL-35-1500-5 1500 5% 0.674 30.00 1515 13.8 1700 750 1510 1550
XKGKL-35-1500-8 8% 1.078 18.75 2424 17.9 1820 800 1620 1910
XKGKL-35-1500-10 10% 1.347 15.00 3031 20.7 1800 900 1600 2200
XKGKL-35-1500-12 12% 1.617 12.50 3637 23.2 2300 900 2110 2380
Fields of application

The reactor is mainly used in the power system, to adjust the reactive power distribution in the system, reduce the power frequency voltage, and suppress the harmonic current and flicker. The following are some common applications: 

 1. In the power system: The reactor plays the role of regulating the reactive power in the power system, which can improve the stability of the system. For example, installing a parallel reactor in a transmission line can balance the reactive power and reduce line loss; installing a series reactor in a transformer can reduce the no-load current and extend the life of the equipment. 
  
 2. In the motor system: the reactor can be used during the starting and braking of the motor to reduce the starting current and the impact current during the braking process. In addition, it can also be used to prevent the self-excited magnetic phenomenon of the motor under light or no-load. 
  
 3. In electronic equipment and communication systems: reactors can be used to suppress the high-order harmonic components in the power supply and reduce the impact on electronic equipment. For example, high-frequency reactors are used in switching power supplies, inverters, communication equipment, etc.
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv

 

After Sales Service

1.Our company provides you with project design and process design, and designs and manufactures products according to your equipment purchase plan and specific needs. And train technical and operating personnel for you.

2.The newly purchased products are provided with online assistance for installation and debugging. The products are under the lifelong service system. If problems occur in normal use, we will provide solutions within one working day after receiving user's feedback. We will try our best to get the product up and running as soon as possible. And there are regular visits by professional technicians to ensure the long-term, safe and reliable use of our products.

3.We use quality authentic materials, process and manufacture in strict compliance with ISO9001:2000 international quality management to ensure the quality of excellence and the smooth installation!
 

Packaging & Shipping

 

Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
 
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
 
FAQ

 

Shunt Reactor, Current-Limiting Reactor 6kv/10kv/20kv
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier