Customization: | Available |
---|---|
Certification: | CCC |
Shell Material: | Stainless Steel |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Henan Energy Electric Equipment Co., Ltd. was established in 2011 and is an excellent and reliable power equipment manufacturer in China. The company mainly develops and produces oil-immersed transformers, dry-type transformers, box-type substations, high-voltage switches, and medium and low voltage complete sets of equipment. The equipment put into production and operation of the project advocates energy saving, intelligence, informatization, and mechanization. The company has established the Henan Triangle Energy-saving Transformer Engineering Technology Research Center, with 71 utility model patents and 15 invention patents. With years of accumulation in the transformer industry and strong technological innovation capabilities, HZEC products are sold to the Middle East, North America, South America, Europe, Southeast Asia, Africa, and other regions, covering more than 40 countries.
1. Indoor/outdoor ;
2. Ambient air temperature :-30ºC~+40ºC;
3. Altitude: does not exceed 1000m;
4. Relative humidity: the daily average is not more than 95%, the monthly average is not more than 90%;
5. The magnitude of the earthquake was no more than 8 degrees;
6. No fire, explosion, serious pollution, chemical corrosion and violent vibration.
7. Wind speed: no more than 35m/s.
No. | Item | Unit | Data | ||||||||||||||||||
1 | Rated voltage | KV | 72.5 | ||||||||||||||||||
2 | Rated current | A | 1250,1600,2000,3150 | ||||||||||||||||||
3 | Rated frequency | Hz | 50 | ||||||||||||||||||
4 | Rated peak withstand current | KA | 100 | ||||||||||||||||||
5 | Rated short-time withstand current | 40 | |||||||||||||||||||
6 | Rated lightning impulse withstand voltage | KV | 325 | ||||||||||||||||||
7 | Rated power frequency withstand voltage | 140 | |||||||||||||||||||
8 | Gas pressure (20ºC) | MPa | circuit breaker 0.6/others 0.5 | ||||||||||||||||||
9 | Annual leakage rate of SF6 gas | % | ≤0.5 | ||||||||||||||||||
10 | Moisture content of gas compartment | Circuit breaker | uL/L voltage ratio |
≤150 | |||||||||||||||||
Other components | ≤250 | ||||||||||||||||||||
11 | Circuit breaker | ||||||||||||||||||||
Operating mechanism | Spring mechanism | ||||||||||||||||||||
Rated short-circuit breaking current | KA | 40 | |||||||||||||||||||
Rated cycle of operation | O-0.3s-CO-180s-CO | ||||||||||||||||||||
12 | Disconnector | ||||||||||||||||||||
Operating mechanism |
Manual and motor operated;
3-pole mechanically group operated
|
||||||||||||||||||||
Switching ability of breaking and making busbar current |
Switching current | A | 1600 | ||||||||||||||||||
Conversion voltage | V | 10 | |||||||||||||||||||
Breaking time | Time | 100 | |||||||||||||||||||
13 | Fault making earthing switch | ||||||||||||||||||||
Rated making current (peak) | kV | 100 | |||||||||||||||||||
Rated short-time withstand current (4s) | kA | 40 | |||||||||||||||||||
Type of operating mechanism | Manual, motor-driven spring; 3-pole mechanically group operated | ||||||||||||||||||||
14 | Earthing switch for maintenance | ||||||||||||||||||||
Rated short-time withstand current (4s) | kA | 40 | |||||||||||||||||||
15 | Voltage transformer | ||||||||||||||||||||
Technical parameters | As per requirements of customers | ||||||||||||||||||||
16 | Current Transformer | ||||||||||||||||||||
Technical parameters | As per requirements of customers | ||||||||||||||||||||
17 | Lightning arrester | ||||||||||||||||||||
Technical parameters | According to IEC 60099-1 "MOA" |
1. Small unit size, light weight, excellent anti-seismic performance;
2. Reliable conductivity;
3. High reliability of insulation;
4. Excellent SF6 gas systems and sealing technology;
5. High breaking capacity;
6. Satisfying the needs of smart grid;
7. Use of standardized, modular design and production.