Customization: | Available |
---|---|
Task: | Monitoring |
Structure: | Open-Loop |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | SI48Y | S3I48 | SU48Y | S3U48 | SI72Y | S3I72Y | SU72Y | S3U72Y | SI96Y | S3I96Y | SU96Y | S3U96Y |
Panel size (48x48mm) | YES | YES | YES | YES | NO | NO | NO | NO | NO | NO | NO | NO |
Panel size (72x72mm) | NO | NO | NO | NO | YES | YES | YES | YES | NO | NO | NO | NO |
Panel size (96x96mm) | NO | NO | NO | NO | NO | NO | NO | YES | YES | YES | YES | |
1-phase current | YES | NO | NO | NO | YES | NO | NO | NO | YES | NO | NO | NO |
3-phase current | NO | YES | NO | NO | NO | YES | NO | NO | NO | YES | NO | NO |
1-phase voltage | NO | NO | YES | NO | NO | NO | YES | NO | NO | NO | YES | NO |
1-phase voltage | NO | NO | NO | YES | NO | NO | NO | YES | NO | NO | NO | YES |
RS485 Port (C) | Optional | NO | Optional | NO | Optional | Optional | Optional | Optional | Optional | Optional | Optional | Optional |
Analog output (M) | Optional | NO | Optional | NO | Optional | Optional | Optional | Optional | Optional | Optional | Optional | Optional |
Relay Output (J) | NO | NO | NO | NO | Optional | Optional | Optional | Optional | Optional | Optional | Optional | Optional |
Digital Input (K) | NO | NO | NO | NO | Optional | Optional | Optional | Optional | Optional | Optional | Optional | Optional |
Accuracy | 0.5% (default), 0.2% | |
Date Update Rate | 1s | |
Input |
Current | Rated value:AC 1A, 5A |
Voltage | Rated value: AC 100V, 220V, 400V etc | |
Overload | Continuous: 2 times of rated value | |
Frequency | 45-65Hz | |
Safe Power Supply |
Range | AC 80-270V 50/60Hz, DC 100-350V |
Consumption | ≤5VA | |
Digital Input | 2 dry contact inputs, isolation: 2kVAC | |
Relay Output | 2 relay outputs, contact rated at AC 5A/250V or DC 5A/30V, isolation:2kVAC | |
Analog Output | DC 4-20mA, load≤350Ω DC 0-5V, load≥20kΩ | |
Communication Port | RS485, Modbus-RTU, 2-wire, up to 9600 bps | |
Degree of Protection | Front: IP64, Rear: IP20 | |
Operating Temperature | -40ºC-70ºC(LED -25ºC-70ºC (LCD) | |
Storage Temperature | -45ºC-85ºC(LED), -30ºC-80ºC (LCD) | |
Relative Humidity | ≤93%RH | |
Insulation | ≥2kVAC | |
Altitude | ≤2500m |
Measuring Accuracy | Communication | Inputs and Outputs |
-Voltage: 0.2%/0.5% -Current: 0.2%/0.5% -Overload: 2 times of rated value |
-Interface: RS485 -Protocol: Modbus-RTU |
-2 digital inputs -2 relay outputs -1 analog output |
Dimensions Typical Wiring