Henan Energy Electric Equipment Co., Ltd. was established in 2011 and is an excellent and reliable power equipment manufacturer in China. The company mainly develops and produces oil-immersed transformers, dry-type transformers, box-type substations, high-voltage switches, and medium and low voltage complete sets of equipment. The equipment put into production and operation of the project advocates energy saving, intelligence, informatization, and mechanization. The company has established the Henan Triangle Energy-saving Transformer Engineering Technology Research Center, with 71 utility model patents and 15 invention patents. With years of accumulation in the transformer industry and strong technological innovation capabilities, HZEC products are sold to the Middle East, North America, South America, Europe, Southeast Asia, Africa, and other regions, covering more than 40 countries.

Product Description
FEG lightning protection insulator is a kind of two-in-one products of combined structure. It adopts the principle of plugging first and then passing, which enhances the insulation performance and anti-pollution level. It is suitable for the insulation support of overhead lines, and has the protection functions of preventing overhead insulated wires from being broken by lightning, porcelain insulators from blowing up and reducing lightning trip.
Standards: IEC, GB, BS, ANSI, AS or as per requirement of customers.
Service Environment
1. Temperature range : porcelain insulators are suitable for environments where the ambient temperature is between -40ºC and +40ºC.
2. Altitude :The elevation of the installation site shall not exceed 1000m.
3. Voltage class : suitable for power systems with nominal voltage higher than 1000V.
4. Environmental conditions : suitable for common areas and medium and heavy pollution areas .
5. Frequency: No more than 100Hz.
Product Parameters
Model |
Traverse area(mm2) |
Remarks |
FDL-50/240 |
50-240 |
Puncture type |
FDL-50/240B |
50-240 |
Non-puncture type |
1. Lightning full wave impulse withstand voltage (peak)kV:100;
2.1min power frequency withstand voltage (RMS)kV:50;
3. Power frequency arc current (RMS)kA:12.5;
4. Rated bending tolerance load :5kN;
5. Minimum nominal creepage distance :360mm;
6. Apply a unique waterproof insulating paste to the piercing site.
Certifications