Customization: | Available |
---|---|
After-sales Service: | Available |
Warranty: | Two Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Display Mode | 720C: LCD; 720: TFT | |
Accuracy V/A 0.2% | ||
P/Q/S/PF | 0.5% | |
F ±0.01Hz | ||
±kWh | Class 0.5S | |
±kvarh Class 2 | ||
Voltage Input | Rated value | AC 100V,AC 380V |
Overload Continuous:1.2Vn Instantaneous:2Vn/10s | ||
Burden | ≤0.1VA (per phase) | |
Impedance ≥1.7MΩ | ||
Frequency | 45Hz~65 Hz | |
Current Input | Rated value AC 1A, AC 5A | |
Overload | Continuous:1.2In Instantaneous:2In/5s | |
Burden ≤0.2VA (per phase) | ||
Impedance | ≤20mΩ | |
Auxiliary Supply Consumption ≤5VA | ||
Working range AC 80-270V 50/60Hz, DC 100-350V | ||
Communication Port | RS485,Modbus-RTU,2-wire,up to 38.4kbps | |
Energy Pulse Output 1 photocoupler output,pulse width (80±20%)ms | ||
Digital Input | 2 AC wet contact inputs,Isolation:5kVAC | |
Relay Output | 2 relay outputs,Contact rated at AC 5A/250V or DC 5A/30V,Isolation:2kVAC |
|
Environment Conditions | Operating temperature | -25ºC~70ºC |
Storage temperature -30ºC~80ºC | ||
Relative humidity | ≤93% | |
Altitude ≤2500m | ||
Insulation | ≥2kVAC | |
IP Degree Front IP54, Rear IP20 |
Networks | Communication | Accuracy | Data Log | Power Quality | Optional Modules |
-TN, TT, IT networks | -Modbus-RTU -Modbus-TCP -Profibus-DP |
-Active energy: 0.2s -Voltage:0.1% -Current: 0.1% |
-Demand record -Max./Max. value record -Off-limit record -SOE record |
-THD -Harmonics up to 63rd -Unbalance -Sequence component -Crest factor and K factor -Waveform display -Flicker -Transient (Only 720) |
-FM1(2 AC digital inputs) -FM2(4 dry digital inputs) -FM3(2 relay outputs) -FM4(2 analog inputs) -FM5(2 temperature inputs) -FM6(2 analog outputs) -FM7(Modus-TCP) -FM8(Profibus-DP V0) -FM9(WiFi) -FM10(GPRS) -FM11(RS485,Modbus-RTU) -FM12 (M-Bus communication) -FM13(BACnet/MSTP communication) -FM14 (BACnet/IP communication) -FM15(RS232,Modbus-RTU) |
Measuring | Power Quality | Energy Metering | ||
-Fundamental V/A/P/Q/S -Demand -Max./Min.Value -Load profile |
-Harmonics up to 63rd -Sequence component -Unbalance -Crest factor and Kfactor -Phasor diagram |
-Bi-directional energy -Four-quadrant reactive energy -Tariff energy -Fundamental energy |
||
Extension Functions | ||||
GPRS | M-Bus | WIFI | BACnet/IP | RS232 |
Modbus-TCP | Modbus-RTU | 2 relay outputs | BACnet/MSTP | Profibus-DP |
2 analog outputs | 4DC digital inputs | 2 AC digital inputs | 2 analog inputs (4-20mA) | 2 analog inputs (PY100) |
Dimensions
Typical Wiring