CAS No.: | 64742-53-6 |
---|---|
Formula: | C12h11o2 |
Appearance: | Liquid |
Item |
GB 2536-2011 1-10ºC (General) |
Test Method | Value | ||
China | International | ||||
LCSET/ºC | -10 | GB2356 | IEC 60296 | - | |
Functional characteristics | |||||
Kinematic viscosity,(40ºC),mm2/s | ≤12 | GB/T 265 | IS0 3014 | 9.864 | |
Kinematic viscosity,(-10ºC),mm2/s | ≤1800 | GB/T 265 | IS0 3014 | 164.2 | |
Tilt point/ºC | ≤-20 | GB/T 3535 | IS0 3016 | -27 | |
Water content/(mg/kg) | ≤30 | GB/T 7600 | IEC 60814 | 20 | |
Breakdown voltage / (kV) | Unprocessed | ≥30 | GB/T 507 | IEC 60156 | 38 |
Processed | ≥70 | GB/T 507 | IEC 60156 | >70 | |
Density (20ºC)/(kg/m3) | ≤895 | SH/T 0604 | ISO 12185 | 883.8 | |
Dielectric loss factor (90ºC) | ≤0.005 | GB/T 5654 | IEC 60247 | <0.001 | |
Refining/Stability | |||||
Appearance | Clear and transparent, without sediment and suspended matter | GB 2536 | IEC 60296 | Clear and transparent, without sediment and suspended matter | |
Acid value/(mgKOH/g) | ≤0.01 | NB/SH/T 0836 | IEC 62021-1 | <0.01 | |
Interfacial tension/(mN/m) | ≥40 | GB/T 6541 | ASTM D971 | 45 | |
Corrosive sulfur | Non-corrosive | SH/T 0804 | DIN 51353 | Non-corrosive | |
Total sulfur content (mass fraction)% | No general requirements | SH/T 0689 | ASTM D5453 | <0.01 | |
Water-soluble acid or alkali | None | GB/T 259 | None | ||
Antioxidant additive content/% | 0.08-0.40 | SH/T 0802 | IEC 60666 | 0.3 | |
2-furfural content/(mg/kg) | ≤0.1 | NB/SH/T 0812 | IEC 61198 | <0.05 | |
Operating characteristics | |||||
Oxidation stability (120ºC, 500h) | |||||
Total acid value/(mgKOH/g) | ≤1.2 | NB/SH/T 0811 | IEC 61125C | 0.12 | |
Oil sludge (mass fraction)/% | ≤0.8 | NB/SH/T 0811 | IEC 61125C | 0.02 | |
Dielectric loss factor (90ºC) | ≤0.500 | GB/T 5654 | IEC 60247 | 0.053 | |
Health, Safety and Environmental Features | |||||
Flash point (closed cup)/ºC | ≥135 | GB/T 261 | ISO 2719 | ||
Condensed ring aromatic hydrocarbons (PCA) content/% | ≤3 | NB/SH/T 0838 | IP 346 | ||
Polychlorinated biphenyls (PCB) content/(mg/kg) | Not detected | SH/T 0803 | IEC 61619 | Not detected |
1. Preferred cycloalkane crude oil with low aromatics, low sulfur content and low freezing point is used as raw material;
2. Excellent electrical insulation performance, high breakdown voltage and low dielectric loss factor can effectively prevent discharge and power loss under high voltage electric field, and meet stringent insulation performance requirements;
3. Higher cycloalkane and appropriate aromatic content can dissolve acidic sludge formed during long-term operation of equipment or overheating failure to avoid damaging solid insulation materials and affecting heat transfer and insulation performance;
4. Low viscosity and viscosity index provide effective cooling and heat transfer;
5. Excellent thermal stability and oxidation stability, which can prevent oil aging to the greatest extent, extend the service life of equipment and reduce maintenance costs;
6. Adopt advanced processing technology, environmentally friendly, and do not contain polyfluorinated biphenyls.