Model | Rated voltage of transformer(kV) | Neutral point withstand voltage | Disconnector | Oxide zinc arrester | Discharging gap | Current transformer | ||||||
Lightning full wave and chopped impulse withstand voltage (kv) | 1min power frequency(kV) | Rated current (A) | Operational mechanism | Rated voltage (kV) | Continuous working voltage (kV) | DC 1mA reference voltage ≥ | 8/20µs lightning impulse residual current (kV) | Power frequency discharging voltage(kV) | Type test | Transformation ratio | ||
BJB-110 | 110 | 250 | 95 | 400 | CS8-5 (manual) or CJ6 (Electrical) |
72 | 58 | 103 | 186 | 83 | Epoxy resin poured completely enclosed pillar type 10kV (110/5, 200/5, 300/5, 400/5, 500/5, 600/5) | |
BJB-220 | 220 | 400 | 200 | 600 | 144 | 116 | 205 | 320 | 166 |
1. Suitable for indoor and outdoor;
2. Ambient temperature: not lower than -40ºC, not higher than +55ºC; Relative humidity: not more than 95% (25ºC);
3. The altitude does not exceed 3000m, beyond 3000m can be customized according to the actual situation;
4. Areas with seismic intensity of 7 degrees and below; Wind speed does not exceed 35m/s;
5. Power grid frequency: 58 ~ 62Hz (60Hz system), 48 ~ 52Hz (50Hz system);
6. The air in the installation site should not contain chemical gases and vapors, and there is no dust.
1. The device can be lifted using the four mounting holes in the base. Do not bind the lifting rope to the porcelain column to prevent damage to the device.
2. The channel steel bracket for fixing the operating mechanism and the steel pipe from the operating mechanism to the rotating shaft of the conductive rod of the isolation switch are not within the scope of supply of this device. All are made by the installation unit on site, and the length and size are determined on site.
3. The device should be grounded reliably.
4. The shape and size of the product shall be subject to the actual supply.
5. Install the isolation switch according to the installation instructions of GW8 or GW13 series neutral point isolation switch.