Customization: | Available |
---|---|
After-sales Service: | Available |
Warranty: | Two Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Display Mode | LCD | |
Accuracy V/A 0.2% | ||
P/Q/S/PF | 0.5% | |
F ±0.01Hz | ||
±kWh | Class 0.5S | |
±kvarh Class 2 | ||
Voltage Input | Rated value | AC 100V,AC 380V |
Overload Continuous:1.2Vn Instantaneous:2Vn/10s | ||
Burden | ≤0.1VA (per phase) | |
Impedance ≥1.7MΩ | ||
Frequency | 45Hz~65 Hz | |
Current Input | Rated value AC 1A, AC 5A | |
Overload | Continuous:1.2In Instantaneous:2In/5s | |
Burden ≤0.2VA (per phase) | ||
Impedance | ≤20mΩ | |
Auxiliary Supply Consumption ≤5VA | ||
Communication Port | RS485,Modbus-RTU,2-wire,up to 38.4kbps | |
Energy Pulse Output 1 photocoupler output,pulse width (80±20%)ms | ||
Digital Input | 2 AC wet contact inputs,Isolation:5kVAC | |
Relay Output | 2 relay outputs,Contact rated at AC 5A/250V or DC 5A/30V,Isolation:2kVAC |
|
Environment Conditions | Operating temperature | -25ºC~70ºC |
Storage temperature -30ºC~80ºC | ||
Relative humidity | ≤93% | |
Altitude ≤2500m | ||
Insulation | ≥2kVAC | |
IP Degree Front IP54, Rear IP20 |
1. Measuring:
Demand;
Max./Min.Value;
2. Energy Metering:
Bi-directional energy;
Four-quadrant reactive energy;
Tariff energy (720B);
3. Power Quality(720B):
Harmonics up to 51st;
Sequence component;
Unbalance;
Crest factor and K factor;
Dimensions Typical Wiring