Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item |
Unit |
Type | |
TD-40.5/1250-31.5/G | TD-40.5/1250-25/G | ||
Rated frequency | Hz | 50 | |
Rated voltage | kV | 40.5 | |
Short-time(1 min) power frequency withstand voltage | kV | 118 | |
Lightning impulse withstand voltage (peak) | kV | 215 | |
Rated current | A | 1250 | 1250 |
Rated short-circuit breaking current | kA | 31.5 | 25 |
Rated short-time withstand current | kA | 31.5 | 25 |
Rated peak withstand current | kA | 80 | 63 |
Rated short-circuit making current | kA | 80 | 63 |
Rated single capacitor bank breaking current | A | 630 | |
Rated back-to-back capacitor bank breaking current | A | 400 | |
Rated duration of short-circuit | s | 4 | |
Circuit resistance at min. rated contact force | uΩ | ≤14 | |
Contact cloased force due to bellows and atmosphere | N | 210±45 | |
Counterforce of contact at full stroke | N | 300±50 | |
Mass of moving parts | kg | 2.2 | |
Mechanical endurance | Times | 10000 | |
Contact limit erosion | mm | 3 | |
Switching operation of rated short-circuit breaking current | Times | 30 | |
Shelf life | Years | 20 | |
Internal gas pressure | Pa | <1.33X10-3 | |
Rated operating sequence | O-0.3s-CO-180s-CO | ||
Average opening speed (first 12 mm) | m/s | 1.6±0.2 | |
Average closing speed (last 6 mm) | m/s | 0.8±0.2 | |
Contact bounce duration at closing operation | ms | ≤3 | |
Clearance between open contacts | mm | 18±1 | |
Out of simultaneity of contact closing and opening | ms | ≤2 | |
Rated contact pressure | N | 3200+300 | 3200+300 |
Added external contact forecc at contact touch point | N | 2400+200 | 2400+200 |
Max. rebound during opening | mm | ≤3 |
1. High arc extinguishing efficiency;
2. High operation reliability;
3. Small shape, light weight;
4. Connect and disconnect fast, high reliability;
5. Long life and low maintenance cost.