Customization: | Available |
---|---|
Application: | Power, Electronic, Instrument, Lighting, Audio, Ore |
Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Henan Energy Electric Equipment Co., Ltd. was established in 2011 and is an excellent and reliable transformer manufacturer in China. The company mainly develops and produces oil-immersed transformers, dry-type transformers, box-type substations and high and low voltage complete sets of equipment.The equipment put into production and operation of the project advocates energy saving, intelligence, information and mechanization. The company has established the Henan Triangle Energy-saving Transformer Engineering Technology Research Center,with 71 utility model patents and 15 invention patents.With years of accumulation in the transformer industry and strong technological innovation capabilities, HZEC products are sold to the Middle East, North America, South America, Europe, Southeast Asia, Africa and other regions, covering more than 40 countries.
This product is widely used in areas where it is particularly suitable for use in locations where fire protection is high, such as mines, oil fields, subways, power plants, schools, hospital, commercial centers, high-rise buildings and all within in the configuration system.
The glass fiber and other insulating materials for winding coils have self-extinguishing characteristics, which will not produce arcs due to short circuits, and the resin will not produce toxic and harmful gases under high heat.
Low loss: It has excellent energy-saving effect, economical operation and maintenance-free.
Loss noise: The noise level of the product is more than 10-15dB lower than the current professional standard JB-T10088-2024 "6-220kV transformer sound level".
Low partial discharge: The resin mixture adopts the most advanced mixing method and vacuum film degassing technology, which makes the mixture mix uniformly and completely excludes the air bubbles in the mixture. The product only has vely low partial discharge. High and low voltage coils are cast under vacuum and pressure, so that the resin insulation has both full encapsulation and layer turn-to-turn impregnation. The casting body has a dense cured structure, flame retardant, explosion-proof, and does not pollute the environment.
High mechanical strength: The resin with filler makes the coefficient of expansion difference within the casting body is small, the curing shrinkage rate is small, the internal stress is small, the hardness of the cured material is high, in the internal and external surfaces of the epoxy resin encapsulation layer of the high-voltage and low-pressure coils, there is a prefabricated reinforcing material placed in the layer, which has the same dense structure as the reinforced concrete, and thus the mechanical strength is greater than that of the pure epoxy resin, and it can withstand the action of sudden short-circuit electric force without any demage.
20kV 50kVA-2500kVA off-circuit tap-changing distribution transformer
Rated capacity(kVA) | High voltage combination | Vector group | No-load loss(kW) | Load loss(kW)/155ºC(F)120ºC | No-load current(%) | Impedance(%) | ||
HV(kV) | Tap range(%) | LV(kV) | ||||||
50 | 20; 22; 24 |
±5 or ±2x2.5 |
0.4 | Dyn11 or Yyn0 |
0.340 | 1.2 | 2.0 | 6.0 |
100 | 0.540 | 1.99 | 1.8 | |||||
160 | 0.670 | 2.47 | 1.5 | |||||
200 | 0.730 | 2.94 | 1.5 | |||||
250 | 0.840 | 3.42 | 1.3 | |||||
315 | 0.970 | 4.08 | 1.3 | |||||
400 | 1.15 | 4.84 | 1.1 | |||||
500 | 1.35 | 5.79 | 1.1 | |||||
630 | 1.53 | 6.84 | 1.0 | |||||
800 | 1.75 | 8.2 | 1.0 | |||||
1000 | 2.02 | 9.78 | 0.85 | |||||
1250 | 2.38 | 11.5 | 0.85 | |||||
1600 | 2.79 | 13.8 | 0.85 | |||||
2000 | 3.24 | 16.3 | 0.70 | |||||
2500 | 3.87 | 19.3 | 0.70 | |||||
2000 | 3.24 | 17.8 | 0.70 | 8.0 | ||||
2500 | 3.87 | 21.2 | 0.70 |
35kV 50kVA-2500kVA off-circuit tap-changing distribution transformer
Rated capacity(kVA) | High voltage combination | Vector group | No-load loss(kW) | Load loss(kW)/155ºC(F)120ºC | No-load current(%) | Impedance(%) | ||
HV(kV) | Tap range(%) | LV(kV) | ||||||
50 | 35; 36; 37; 38.5 |
±5 or ±2x2.5 |
0.4 | Dyn11 or Yyn0 |
0.45 | 1.42 | 2.3 | 6.0 |
100 | 0.63 | 2.09 | 2 | |||||
160 | 0.79 | 2.81 | 1.5 | |||||
200 | 0.88 | 3.32 | 1.5 | |||||
250 | 0.99 | 3.8 | 1.3 | |||||
315 | 1.17 | 4.51 | 1.3 | |||||
400 | 1.37 | 5.41 | 1.1 | |||||
500 | 1.62 | 6.65 | 1.1 | |||||
630 | 1.86 | 7.69 | 1 | |||||
800 | 2.16 | 9.12 | 1 | |||||
1000 | 2.43 | 10.4 | 0.75 | |||||
1250 | 2.83 | 12.7 | 0.75 | |||||
1600 | 3.24 | 15.4 | 0.75 | |||||
2000 | 3.82 | 18.2 | 0.75 | |||||
2500 | 4.45 | 21.8 | 0.75 |
Note: Note: The load loss listed in the table is the value of the reference temperature of different insulation systems in brackets (see GB 1094.11). The load loss at the temperature of other insulation systems not included in the table shall be converted according to the respective reference temperature and the data of the insulation system temperature of "155 ºC(F)" as a reference.
The above data is for reference only, our company reserves the right to change the data.
Our company can provide non-standard products according to user requirements.
1. Installation height: altitude is not exceeding 2000m;
2. Waveform of the supply voltage: similar to a sine wave;
3. Summetry of multiphase power supply voltage: the power supply voltage connected to the multiphase transformer should be approximately symmetrical;
4. Ambient temperature: -50ºC-+50ºC.